Trouble
Shooting BD Compressor Systems 12 and 24 Volt
(click here for printable PDF version of this page)
Determine the Model. The data plate is on the left end near the wiring entrance.
BD - BD air* TW - Tradewinds
air**
BDAW - BD air/water TWAW - Tradewinds air/water
BDXP - BDxp air
TWXP - Tradewinds xp air
BDXPAW - BDxp air/water
TWXPAW - Tradewinds xp air/water
BDXPXAW - BDxpx air/water
TWXPXAW - Tradewinds xpx air/water
* All BD systems use re-make-able quick connects and the
systems are pre-charged.
** All Tradewinds systems have Swagelok fittings and remote receiver filter
drier.
Freezers have two plates.
Freezer Bins have two plates in a single construction.
Thermostats: Basic
on the cold plate or bin.
Remote black panel with snowflakes.
ETT digital with temperature readout.
Check for fan operation. Fan will stop momentarily
when the compressor starts.
Check for fault code on the small red LED on the
data plate end of the cabinet. Early
units had internal LED or none.
Note:
Do not apply battery power to any Compressor Module terminals other than
the top two labeled with a large (-) (+). Doing so may destroy the Module.
Trouble Shooting Table for BD & TW Compressor Systems
|
Symptom |
Possible cause |
Check & Test |
Remedies |
|
Totally
Dead: If
no flashes start with step A. |
Faulty Thermostat Step A:
Make sure the thermostat and power are on. Is the
thermostat on? Does it “click” when switching to off?
No! |
By pass the thermostat
at the compressor. Connect
terminals T and C or the connectors at the end of the yellow speed
resister harness if fitted. Thermostats are make
and break switches. Use an ohmmeter to check thermostat wires for
continuity (on). |
If Compressor and fan
run replace the thermostat. If compressor and fan
still do not run, go to step B. |
|
Totally Dead: Single Flash |
No power to unit Step B:
Do you have power to the unit? Power cables could be
reversed. Note:
Do not apply battery power to any Compressor Module terminals other than
the top two labeled with a large (-) (+). Doing so may destroy the Module.
|
Measure the battery
voltage at the compressor connections. If The Unit Has Power the fan will run or the fault
light will flash when switched on and power is available. Check for fault code on the small red LED on the
data plate end of the cabinet. Early
units had internal LED or none. Single flash
is low voltage when trying to start.
|
Check voltage or start
charging batteries to raise the voltage. Also check for loose wires or a
corroded connection. Check amp draw to
confirm that the compressor is operating. |
|
Totally
Dead: Two Flashes |
Faulty
Fan |
Check for
fault code on the small red LED on the data plate end of the cabinet.
Early units had internal LED or none. Two
flashes means the fan
circuit is over loaded. |
Unplug
the fan to see if the compressor starts and fault is corrected.
If the compressor runs replace the fan.
All units use a 12-volt fan (even 24 volt systems). |
|
Symptom |
Possible
cause |
Check
& Test |
Remedies |
|
Compressor does not
start: Three Flashes |
Overcharged Faulty
module Three Flashes: This
fault may also occur when the compressor is trying to start a warm system.
Several attempts and then start up can be normal. |
Check for fault code on the small red LED on the
data plate end of the cabinet. Early
units had internal LED or none. Three flashes.
The compressor may be overloaded by excessive refrigerant charge. Has
charge been added? This fault
can also occur if wiring is weak or switch contacts are worn. The
compressor cannot get up to speed on low voltage.
|
If charge has been
added, remove some refrigerant until flashing stops. If three flashes show
and charge has not been added, i.e. the compressor has been working well,
then the module is weak and will need to be replaced. |
|
Partial Cooling: Frost will form on the coldest place first. This frost is moisture. Moisture will eventually leave suspension and the air in the cabinet will become very dry after a time. Check the temperature of the cold plate(s) not the frost level or amount of coverage. Sometimes only one plate in a freezer will be frosted for it has picked up all the moisture. |
Expansion
valve setting : The expansion valve is
the brass device connected to the cold plate or one of the freezer plates.
It is under a cover on the single plate systems and the Freezer
Bin. Low on refrigerant
|
Remove the cover as
needed by removing all related screws and perhaps the thermostat knob if
so fitted. The expansion
valve has a plastic moisture cap on it that will have red heat shrink on
it until it is first adjusted in the field. Tradewinds will not have the
heat shrink. Remove the heat
shrink by cutting it away with a small knife.
Do not cut into the plastic cap.
Remove, by unscrewing, counterclockwise, the cap, being careful not
to squeeze the brass knob under it and turning it.
Mark the brass knob with a marker in order to return it to this
position if needed. |
First test: Turn
the adjustment knob ¼ turn clockwise and replace the moisture cap.
Be sure the cap seals against the rubber “O” ring.
Observe the cooling on the cold plate.
More of the cold plate should cool if the compressor remains on.
If no noticeable increase in cooling is indicated within an hour
the system is low on refrigerant.
Re-set the valve to the original position and re-cap it. Refer to
re-charging instructions. Leak check and add or
re-charge with refrigerant. |
|
Symptom |
Possible cause |
Check & Test |
Remedies |
| Four and Five Flashes |
Lack
of airflow Excessive
heat |
Four and five flashes
would indicate lack of air or excessive operating temps like an enclosed
locker or hot engine space. Check the water pump
if air and water-cooled. |
This fault will
correct itself when the unit cools off. |
|
Compressor is noisy |
Excessive refrigerant
charge Air in the
system |
The compressor is
silent. Any audible noise has
been tracked to excessive refrigerant charge or air introduced to it by
leaks or improper servicing.
|
Fix: Evacuate
and re-charge with the correct amount of refrigerant. |
|
Compressor will not turn off |
Faulty
Thermostat Incorrect
Thermostat probe installation |
Check
that the compressor will turn off with the thermostat knob in the off
position. Remote Thermostats
work best when any excess capillary tube is in the cold space. If the thermostat is a Remote or ETT the bulb must
be clipped on the side or bottom of the cold plate. The best location would be the coldest section of the
plate. |
If
the compressor does not turn off with the thermostat knob in the off
position, replace the thermostat. Check that the
thermostat bulb is in good thermal contact with the cold plate. The bulb
probe must be on the second plate in a two-plate system. This is the plate
without the valve. |
|
No Cooling: |
Out of Refrigerant |
With
the compressor running for a few minutes some cooling will be evident when
touching the cold plate near or at the expansion valve.
|
See
the following sections: Leak
check and re-charge with refrigerant. |
Monitor the Cabinet Temperature
Start a system with the thermostat in a warm setting. In learning the operation of the control gradually increase the setting over a day to obtain the desired temp. The warmer the box setting is the less power you will use. Make sure the setting you choose allows the compressor to cycle on and off. It is possible in some instances to set the control below the obtainable temperature of the system.
Frost
Frost will form on the coldest place first. This frost is moisture.
Moisture will eventually leave suspension and the air in the cabinet will
become very dry after a time. Check
the temperature of the cold plate(s) not the frost level or amount of coverage.
Sometimes only one plate in a freezer will be frosted for it has picked up all
the moisture.
The cooling process is linear. Refrigerant flows and cools from the expansion
valve through the cold plate. A large plate may not need to be completely active
to cool a small box or one in cooler climates.
A two-plate system will cool the first plate before any cooling starts in
the second one and may not chill all of the second plate before the thermostat
turns the compressor off.
Reference Data Sheets